ESP Addressable and Conventional Fire Protection • www.espuk.com
CONVENTIONAL FIRE PANELS
MAG4P - 4 Zone Fire Panel
4 programmable zones
Active end of line monitoring and head removal
30 fire detectors per zone
Unlimited number of call points per zone
Integral evacuate alarm button
‘Class change’ facility
Enable/disable security key
One man walk test facility
Volt free fire change over relay
Volt free fault change over relay
Individual sounder circuit fault ID
Individual zone/sounder isolate
Cer
tified to
EN54–2/4
Requires only 1x12v battery
MAG4P - ABS casing
Made in
EU
EN54
MAG4 - 4 Zone Fire Panel Metal Casing
OUTPUTS Sounder 1 24V (max 300mA fused)
Sounder 2 24V (max 300mA fused)
Fault/fire relay Volt free 500mA @ 24V (max load)
Auxiliary output 24VDC (300mA fused)
ENVIRONMENT Working Temperature 0 to 40ºC
Storage Temperature -20 to 60ºC
Humidity 0 - 95%
Dimensions MAG4P 340 x 290 x 100mm
Dimensions MAG4 320 x 220 x 80mm
Weight MAG4P - 2.5Kg MAG4 - 3.5Kg
INPUTS Max detectors per zone 30
Thresholds for 0 - 2 mA (Fault condition)
zone conditions 2 - 6 mA (Normal condition)
6 - 110 mA (Fire condition)
110 mA - Short (Fault condition)
POWER Mains fail consumption 50mA
Mains supply 230 VAC ± 10%
Standby supply 1 x 7ah 12V S.L.A. Battery
Power availability 0.7 amps
MAGPro Fireline Catalogue.qxp_Layout 1 16/06/2014 15:35 Page 14